Fixed Orifice Balancing Valve with Isolation Ball Valve | 9517IBV Series | DZR Brass
9517IBV Fixed Orifice Double Regulating Globe Valve with Isolation Ball Valve
The RWV 9517IBV Series combines a DZR brass fixed-orifice double regulating globe valve with an integrated isolation ball valve for hydronic flow measurement, balancing and ON/OFF isolation. The assembly features a Venturi insert, pressure test points, a multi-turn adjustment handwheel and a memory stop.
The valve is designed according to BS7350, with a nominal Cvs tolerance of ±3% when tested according to BS7350. It features union ends for tailpiece connections and is available in .5", .75" and 1" nominal sizes.
Key Features
- Fixed-Orifice Design: Incorporates a Venturi insert for differential-pressure-based flow measurement.
- Integrated Isolation Ball Valve: Provides ON/OFF operation through a ball valve with union nut.
- Memory Stop: Supports returning the balancing handwheel to its preset position after shut-off.
- Multi-Turn Adjustment: Provides a minimum of four full turns of adjustment.
- DZR Brass Construction: Main valve body and Venturi insert use dezincification-resistant brass, UNS C35330.
- Union Connections: Union ends conform to ASME B1.20.1 NPSM for compatible tailpiece connections.
- Connection Options: FNPT, MNPT, Solder, EzPress and PEX (F1960) tailpieces are available for the balancing valve. The isolation ball valve is available with FNPT, Solder, EzPress and PEX (F1960) connections.
- Service Features: Blow-out-proof stem and adjustable packing.
- Pressure Test Points: DZR brass test points with EPDM Perox gaskets and polypropylene ties.
Technical Specifications
| Specification | Manufacturer Information |
|---|---|
| Manufacturer | Red-White Valve Corp. |
| Series | 9517IBV |
| Valve Type | Fixed Orifice Double Regulating Globe Valve with Isolation Ball Valve |
| Body Material | DZR Brass, UNS C35330 |
| Pressure Rating | 300 WOG |
| Water Temperature | 15°F to 260°F, subject to fluid restrictions below |
| Design Standard | BS7350 |
| Nominal Cvs Tolerance | ±3%, tested according to BS7350 |
| Adjustment | Minimum four full turns |
| Union End Standard | ASME B1.20.1 NPSM |
| Available Sizes | .5", .75", 1" |
Working Fluid Restrictions: Below 32°F, water must contain antifreezing fluids. Above 212°F, water must contain anti-boiling fluids, as specified by RWV.
Flow Ranges and Venturi Coefficients
The following are manufacturer-suggested flow ranges for BS7350 applicability. The X, U and L configurations provide different flow characteristics at the .5" nominal size.
| Nominal Size | Flow Version | Suggested Flow Range (GPM) | Venturi Cvs |
|---|---|---|---|
| .5" | Extra-Low (X) | 0.12–0.36 | 0.304 |
| .5" | Ultra-Low (U) | 0.27–0.71 | 0.64 |
| .5" | Low (L) | 0.49–1.17 | 1.33 |
| .5" | Standard | 0.98–2.35 | 3.24 |
| .75" | Standard | 2.19–5.15 | 6.16 |
| 1" | Standard | 4.09–9.56 | 11.24 |
Flow ranges are suggested applicability values, not guaranteed operating flow rates. Confirm that the differential-pressure measuring instrument has sufficient sensitivity for the intended minimum flow.
Connection Configurations
The 9517IBV uses union connections with available tailpiece options. RWV provides dimensional drawings for the following isolation ball valve connection families:
| RWV Drawing Code | Isolation Ball Valve Connection |
|---|---|
| 9517IBV-MF | FNPT |
| 9517IBV-MS | Solder |
| 9517IBV-MP | EzPress |
| 9517IBV-ME | PEX (F1960) |
Select the required size and connection configuration from the available product variants. Refer to the manufacturer specification sheet for connection-specific dimensions and valve weights. Package contents and tailpiece inclusion require confirmation.
Construction Materials
- Valve Body, Venturi Insert and Balancing Cone: DZR brass, UNS C35330.
- Handwheel: Blue ABS.
- Test Points: DZR brass with EPDM Perox gaskets and polypropylene ties.
- Union O-Ring: EPDM Perox, NSF approved as specified by RWV.
- Isolation Ball: Chrome-plated DZR brass.
- Seats and Packing Rings: PTFE.
- Isolation Handle: Steel, plated.
Flow Measurement and Installation
Flow is determined from the differential-pressure signal measured at the valve test points using the applicable Venturi coefficient. RWV provides flow-measurement curves, headloss coefficients and a presetting diagram in the manufacturer specification sheet.
For installation, use pipe with the same nominal size as the valve. RWV specifies a minimum straight upstream pipe length of 5 times the nominal pipe diameter (5 × DN), increasing to 10 × DN when installed at a pump outlet. Follow the manufacturer's installation diagram and instructions.
Manufacturer Documentation
For connection-specific dimensions, valve weights, headloss data, flow-measurement curves and presetting instructions, refer to the RWV 9517IBV Specification Sheet (PDF), revision [201021].
California Proposition 65 Warning
WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.