Fixed Orifice Balancing Valve | 9519 Series | Solder x Solder | Test Points
Fixed Orifice Static Balancing Valve | 9519 Series | Solder x Solder | 300 WOG
The 9519 Series Fixed Orifice Static Balancing Valve is a DZR brass double-regulating globe valve designed for flow balancing in hydronic heating and cooling systems. The valve features a fixed-orifice Venturi insert, solder joint connections, pressure test points and a multi-turn adjustment handwheel with memory stop.
The 9519 Series is designed according to BS7350, with a nominal Cvs tolerance of ±3% when tested according to BS7350. The handwheel provides a minimum of four full turns of adjustment, with positive shut-off and memory-stop functionality for repeatable valve settings.
Key Features & Benefits
- Solder Joint Connections: Solder ends conform to ASME B16.22.
- DZR Brass Construction: Body, Venturi insert and balancing cone are manufactured from dezincification-resistant brass (UNS C35330).
- Fixed-Orifice Venturi Insert: Provides a differential-pressure signal for calculating flow using the appropriate valve coefficient.
- Multi-Turn Handwheel: Provides a minimum of four full turns of adjustment with positive shut-off and memory stop.
- Pressure Test Points: DZR brass test points with EPDM Perox gaskets and polypropylene ties.
- Flow Measurement: Manufacturer-specified nominal Cvs tolerance of ±3%, tested according to BS7350.
- Available Configurations: Standard sizes from .5" through 2", plus X, U and L .5" flow-range configurations.
Pressure & Temperature Ratings
| Specification | Manufacturer Rating |
|---|---|
| Pressure Rating | 300 WOG |
| Water Temperature | 15°F to 260°F |
| Below 32°F | Only with added antifreezing fluids |
| Above 212°F | Only with added anti-boiling fluids |
| Valve Design | BS7350 |
| Connection Standard | ASME B16.22 solder joints |
Solder-End Dimensions & Suggested Flow Ranges
The following dimensions and valve weights apply to the 9519 solder-end configuration. Flow ranges are manufacturer-suggested applicability ranges according to BS7350.
| Size / Version | H (in) | L (in) | B (in) | Valve Weight (lb) | Suggested Flow (GPM) |
|---|---|---|---|---|---|
| X .5" | 4.06 | 3.74 | .55 | 1.16 | 0.12 to 0.36 |
| U .5" | 4.06 | 3.74 | .55 | 1.16 | 0.27 to 0.71 |
| L .5" | 4.06 | 3.74 | .55 | 1.16 | 0.49 to 1.17 |
| .5" | 4.06 | 3.74 | .55 | 1.16 | 0.98 to 2.35 |
| .75" | 4.06 | 4.18 | .76 | 1.34 | 2.19 to 5.15 |
| 1" | 4.06 | 4.57 | .92 | 1.55 | 4.09 to 9.56 |
| 1.25" | 4.85 | 5.28 | .98 | 2.53 | 8.56 to 19.81 |
| 1.5" | 4.94 | 5.90 | 1.10 | 3.16 | 12.84 to 29.80 |
| 2" | 5.34 | 6.73 | 1.35 | 4.46 | 24.09 to 55.63 |
Notes: Dimensions and weights are for the solder-end valve, not shipping packaging. The X, U and L .5" versions have distinct flow ranges. The manufacturer advises verifying manometer sensitivity when measuring near the indicated minimum flow.
Material Construction
| # | Component | Material | Specification |
|---|---|---|---|
| 1 | Body | DZR Brass | UNS C35330 |
| 2 | Venturi Insert | DZR Brass | UNS C35330 |
| 3 | Balancing Cone | DZR Brass | UNS C35330 |
| 4 | Gasket Disc | PTFE | - |
| 5 | Disc* | DZR Brass | UNS C35330 |
| 6 | Disc O-Ring* | EPDM Perox | - |
| 7 | Shutter | DZR Brass | UNS C35330 |
| 8 | Stem O-Ring | EPDM Perox | - |
| 9 | Union* | DZR Brass | UNS C35330 |
| 10 | Stem | Brass | ASTM B124 C37700 |
| 11 | Bonnet | DZR Brass | ASTM C35330 |
| 12 | Stop Spring Ring | Spring Steel | - |
| 13 | Screw | Steel | - |
| 14 | Handwheel | ABS (Blue) | - |
| 15 | Nut | Steel / Zinc Plated | - |
| 16 | Test Point | DZR Brass | UNS C35330 |
* Disc, disc O-ring and union are present only on 1.25", 1.5" and 2" sizes. Test points use EPDM Perox gaskets and polypropylene ties.
Flow Measurement
Flow measurement uses the differential-pressure signal across the valve test points and the applicable Venturi flow coefficient. Select the correct valve version and use the manufacturer's flow-measurement data to determine the flow rate.
For detailed flow coefficients, headloss calculations and handwheel presetting information, refer to the official RWV specification.
Installation Guidance
- Pipe Size: Install the valve in pipework of the same nominal size.
- Upstream Straight Length: Minimum five pipe diameters, or ten pipe diameters when installed at a pump outlet.
- Downstream Straight Length: Minimum two pipe diameters.
- Flow Measurement: Follow the manufacturer instructions for test-point connections, valve presetting and differential-pressure measurement.
Manufacturer Specification
View Official RWV 9517 / 9519 Specification Sheet (PDF)
California Proposition 65 Warning
WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, visit www.P65Warnings.ca.gov.