RED-WHITE VALVE CORP.  |  SKU: 30078364  |  MPN: 9450A 2-1/2

Hydronic Orifice Plate | 9450A Series | Wafer Flange | 316 SS

$195.28
Each
Size

• 316 Stainless Steel Construction: AISI 316 stainless steel body and extensions for hydronic flow measurement.
• Wafer-Style Design: Designed for installation between ANSI 125 or ANSI 150 flanges.
• Differential Pressure Measurement: High- and low-pressure metering points with nominal Cvs tolerance of ±5%, tested according to BS7350.
• Available Sizes: Eight configurations from 2.5" to 12", with manufacturer-suggested flow ranges of 47.9–4,057 GPM across the series.
• Pressure & Temperature: 600 WOG rating and 15°F–260°F water working range, subject to RWV antifreeze and anti-boil fluid requirements.

9450A Hydronic Orifice Plate | Wafer Style | 316 Stainless Steel

The 9450A Series Stainless Steel Orifice Plate is designed for differential-pressure flow measurement in hydronic piping systems. Its wafer-style construction is intended for installation between ANSI 125 or ANSI 150 flanges, with high- and low-pressure metering points for flow measurement.

The orifice plate features an AISI 316 stainless steel body and extensions, DZR brass test points, and a manufacturer-specified pressure rating of 600 WOG. Designed according to BS7350, the 9450A has a ±5% tolerance on nominal Cvs, tested according to BS7350. Eight nominal sizes are available from 2.5" through 12".

Key Features & Benefits

  • 316 Stainless Steel Construction: AISI 316 stainless steel body and extensions.
  • Wafer-Style Flange Design: Designed for use with ANSI 125 or ANSI 150 flanges.
  • High and Low Pressure Metering Points: Differential-pressure test points support flow measurement using the applicable Cvs coefficient.
  • BS7350 Design: Nominal Cvs tolerance of ±5%, tested according to BS7350.
  • Operating Conditions: 600 WOG rating and water working temperatures from 15°F to 260°F, subject to the manufacturer's fluid restrictions.

Pressure & Temperature Specifications

Specification Manufacturer Value
Pressure Rating 600 WOG
Water Temperature 15°F to 260°F, subject to fluid restrictions
Design Standard Designed according to BS7350
Nominal Cvs Tolerance ±5%, tested according to BS7350
Flange Compatibility ANSI 125 or ANSI 150

Working Fluid Restrictions: Below 32°F, use only water with added antifreezing fluids. Above 212°F, use only water with added anti-boiling fluids, as specified by RWV.

Dimensions, Flow Measurement Cvs & Suggested Flow Ranges

The following values are taken from the manufacturer's 9450A dimensional and flow-measurement table. Dimensions are in inches. Listed weights are manufacturer product weights, not verified packaged shipping weights.

Size ØD (in) H (in) L (in) Cvs (Flow Measurement) Product Weight (lb) Suggested Flow (GPM)
2.5" 4.84 5.9 0.7 102.0 3.2 47.9–110.2
3" 5.31 6.2 0.7 142.2 3.9 101.4–243.5
4" 6.42 6.7 0.7 249.3 4.3 172.0–412.7
5" 7.60 7.3 0.7 389.5 5.6 267.1–630.1
6" 8.62 7.8 0.7 530.2 6.5 375.8–902.0
8" 10.79 8.9 0.7 929.5 9.1 663.5–1592
10" 12.99 10.0 0.7 1444 11.8 1055–2485
12" 15.16 11.1 0.7 2122 15.1 1492–4057

The flow ranges shown are suggested applicability values according to RWV's BS7350 data. Cvs values in this table are used for flow measurement and are distinct from the headloss Cv values below.

Headloss Cv Values

RWV publishes the following separate Cv values for calculating theoretical headloss across the orifice plate.

Nominal Size Headloss Cv
2.5" 175.4
3" 261.6
4" 426.3
5" 654.2
6" 901.4
8" 1636
10" 2497
12" 3694

Material Construction

Part Material Specification
Body Stainless Steel AISI 316
Extension Stainless Steel AISI 316
Test Points DZR Brass ASTM C35330

Test points are supplied with EPDM Perox gaskets and polypropylene ties, according to RWV.

Installation & Flow Measurement

Install the 9450A in pipe of the same nominal size as the orifice plate. RWV specifies the following minimum straight-pipe lengths:

  • Upstream: 5 times the nominal pipe diameter.
  • Pump Outlet: 10 times the nominal pipe diameter upstream when installed at a pump outlet.
  • Downstream: 2 times the nominal pipe diameter.

The plate measures flow using the differential-pressure signal at its high- and low-pressure test points. The minimum measurable flow depends on the sensitivity of the manometer used.

Balancing Valve Arrangement: RWV illustrates the 9450A installed together with a 9574P balancing valve of the same nominal size. Refer to the manufacturer's installation diagram for the illustrated arrangement and straight-pipe requirements.

Manufacturer Documentation

For dimensional drawings, flow-measurement curves, headloss data and installation diagrams, refer to the RWV 9450A Specification Sheet (PDF), document code [230930].

California Proposition 65 Warning

WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.