  • 316 Stainless Steel Construction — Provides superior corrosion resistance and durability in hydronic flow-measurement applications.
  • Integrated Pressure Taps — High and low ports allow accurate differential pressure readings for precise flow calculation.
  • Wafer Style ANSI Flange Mount — Installs quickly between ANSI 125/150 flanges with compact form factor.
  • ±5 % Cv Accuracy — Flow ranges from 47.9 to 4,057 GPM depending on size, tested per BS7350 standards.
  • Wide Operating Range — Performs 15 °F to 260 °F at 600 WOG for both chilled and heated water systems.

Hydronic Orifice Plate | 9450A Series | Wafer Style | 316 SS | ANSI 125/150 Flange Mount

9450A Series Stainless Steel Orifice Plates provide precise, repeatable flow measurement for hydronic systems requiring dependable differential-pressure accuracy. Fabricated from corrosion-resistant AISI 316 stainless steel, this wafer-style orifice plate installs easily between ANSI 125 or 150 flanges and includes integrated high- and low-pressure test points for direct flow verification.

Built in accordance with BS7350 standards, the 9450A maintains a ±5 % Cv tolerance and operates at 600 PSI WOG. With a working temperature range of 15 °F to 260 °F, it performs reliably in both chilled and hot water systems, including those treated with antifreeze or anti-boil additives.

Key Features & Benefits

  • 316 Stainless Steel Construction — Resists corrosion and pitting in closed-loop water and glycol applications for long service life.
  • Integrated Pressure Taps — Built-in high/low test ports with EPDM Perox gaskets enable accurate flow measurement per BS7350.
  • Compact Wafer Design — Fits securely between ANSI 125 or 150 flanges with minimal space requirements and fast installation.
  • Wide Operating Range — Handles 15 °F to 260 °F water and glycol mixtures at pressures up to 600 WOG.
  • Tested Cv Accuracy — ±5 % Cv tolerance verified under BS7350 standards; flow rates span 47.9 – 4,057 GPM by size.

Pressure & Temperature Ratings

Pressure Rating Temperature Range
600 PSI WOG 15 °F – 260 °F (antifreeze/anti-boil required below 32 °F or above 212 °F)

Dimensions & Flow Data

Size ØD [in] H [in] L [in] Cv Value Weight [lb] Flow Range [GPM]
2½″ 4.84 5.9 0.7 102 3.2 47.9 – 110.2
3″ 5.31 6.2 0.7 142.2 3.9 101.4 – 243.5
4″ 6.42 6.7 0.7 249.3 4.3 172 – 412.7
5″ 7.60 7.3 0.7 389.5 5.6 267.1 – 630.1
6″ 8.62 7.8 0.7 530.2 6.5 375.8 – 902.0
8″ 10.79 8.9 0.7 929.5 9.1 663.5 – 1592
10″ 12.99 10.0 0.7 1444 11.8 1055 – 2485
12″ 15.16 11.1 0.7 2122 15.1 1492 – 4057

Cv tolerance ±5 %. Suggested flow ranges per BS7350 testing criteria.

Material Construction

# Part Material Specification
1 Body Stainless Steel AISI 316
2 Extension Stainless Steel AISI 316
3 Test Points¹ DZR Brass ASTM C35330

¹ Test points include EPDM Perox gaskets and polypropylene ties.

Installation Guidelines: Install on pipe of matching nominal size with at least 5× diameters of straight run before and after (10× if at pump outlet). May be used with balancing valve RWV 9574P for system calibration.