FIBERGLASS SINGLE EXPANSION JOINT SOCKET X SPIGOT, NO O-RING
The Fiberglass Single Expansion Joint Socket x Spigot is designed to meet the demands of various fiberglass conduit installations, providing flexibility and durability without requiring an O-ring. Ideal for accommodating thermal expansion in long fiberglass conduit runs, these expansion joints offer seamless installation and customization options, making them a versatile choice for a wide range of applications.
Installation Guidelines:
- For ducts shorter than 50 feet, no expansion joint is needed.
- For ducts between 50 and 200 feet, install one expansion joint at the midpoint.
- For ducts longer than 200 feet, install an expansion joint every 200 feet.
- Expansion joints should be positioned as close as possible to the quarter point of the fiberglass conduit span for optimal performance.
Features:
- Easy Installation: Each joint includes a yellow line on the nipple end to ensure correct orientation during installation, speeding up the process.
- Available Types: Choose between fittings for IPS (Iron Pipe Size) and ID (Inside Diameter) to suit your specific fiberglass conduit requirements.
-
Wall Thickness Options:
- Standard Wall (SW) - 0.070"
- Medium Wall (MW) - 0.096"
- Heavy Wall (HW) - 0.110"
- Extra Heavy Wall (XW) - 0.250"
Customization Options:
- Available in standard black and grey, with custom colors available upon request to suit aesthetic or visibility needs.
Certifications & Compliance:
- UL 2420 (Below Ground) and UL 2515 (Above Ground) listed
- ISO 9001:2015 Certified for quality management
- ISO 14001:2015 Certified for environmental management
- ISO 45001:2018 Certified for occupational health and safety
Our Fiberglass Single Expansion Joint Socket x Spigot connectors, adapters, and couplings are engineered for both performance and versatility, ideal for new fiberglass conduit installations or retrofits. These lightweight, robust fittings meet stringent safety and durability standards, making them a dependable choice for a wide range of fiberglass conduit applications.
Nominal Size | Type | IPS Item No Above Ground | A | B | L - MIN | L - MAX | Weight (LBS) | Weight (KG) |
---|---|---|---|---|---|---|---|---|
3/4" | SW | 07C-SW-34 | 1.075" (27) | 12" (305) | 15" (381) | 21" (533) | 0.39 | 0.18 |
1" | SW | 10C-SW-34 | 1.34" (34) | 12" (305) | 15" (381) | 21" (533) | 0.44 | 0.20 |
1-1/4" | SW | 12C-SW-34 | 1.685" (43) | 12" (305) | 15" (381) | 21" (533) | 0.56 | 0.25 |
1-1/2" | SW | 15C-SW-34 | 1.925" (49) | 12" (305) | 15" (381) | 21" (533) | 0.76 | 0.35 |
2" | SW | 20C-SW-34 | 2.400" (61) | 12" (305) | 15" (381) | 21" (533) | 0.87 | 0.40 |
3" | SW | 30C-SW-34 | 3.525" (89) | 12" (305) | 15" (381) | 21" (533) | 1.38 | 0.63 |
4" | SW | 40C-SW-34 | 4.485" (114) | 12" (305) | 15" (381) | 21" (533) | 1.66 | 0.75 |
4" | MW | 40C-MW-34 | 4.537" (115) | 12" (305) | 15" (381) | 21" (533) | 2.07 | 0.94 |
5" | SW | 50C-SW-34 | 5.445" (138) | 12" (305) | 15" (381) | 21" (533) | 2.76 | 1.25 |
5" | MW | 50C-MW-34 | 5.597" (142) | 12" (305) | 15" (381) | 21" (533) | 2.99 | 1.36 |
5" | HW | 50C-HW-34 | 5.625" (143) | 12" (305) | 15" (381) | 21" (533) | 3.00 | 1.36 |
6" | SW | 60C-SW-34 | 6.000" (168) | 12" (305) | 15" (381) | 21" (533) | 3.20 | 1.04 |
6" | MW | 60C-MW-34 | 6.652" (169) | 12" (305) | 15" (381) | 21" (533) | 3.27 | 1.49 |
6" | HW | 60C-HW-34 | 6.680" (170) | 12" (305) | 15" (381) | 21" (533) | 3.75 | 1.70 |